Skip to product information
1 of 1

Honeywell

193 in stock

Honeywell FS-TSFIRE-1624 Field Termination Assembly Module

Honeywell FS-TSFIRE-1624 Field Termination Assembly Module

  • Manufacturer: Honeywell

  • Product No.: FS-TSFIRE-1624

  • Product Type: Field Termination Assembly Module

  • Product Origin: USA

  • Payment: T/T

  • Weight: 1000g

  • Shipping port: Xiamen

  • Warranty: 12 months

Description

The Honeywell FS-TSFIRE-1624 is a high-reliability Field Termination Assembly (FTA) designed for fire-and-gas safety systems within Honeywell’s industrial safety platforms. It provides 16 supervised input channels for connecting fire detectors, manual call points, and other safety field devices. Operating on a stable 24 VDC supply, the module offers built-in line monitoring, short-circuit and open-circuit supervision, and supports end-of-line (EOL) resistors to ensure full loop integrity. Its rugged, compact design, screw-type terminals, and DIN-rail mounting make it suitable for process plants, energy facilities, and harsh industrial environments where high-availability fire detection is required.

Specification

Parameter Description / Value
Power Supply Requirement 24 VDC (external)
Input Voltage Tolerance 24 VDC +25% / –15%
Current Consumption (No Load) Typ. 11 mA at 24 VDC
Number of Input Channels 16 channels
Input Voltage (No Load) Typ. 23.5 VDC at 24 VDC
Channel Resistance 680 Ω ± 5%
Short-Circuit Current 35 mA (at 24 VDC)
Relay Voltage Range 17–39 VDC
Relay Current Consumption Typ. 8.5 mA at 24 VDC
Termination Type Screw terminals
Maximum Wire Diameter 2.5 mm² (AWG 14)
Wire Strip Length 7 mm (0.28 in)
Tightening Torque 0.5 Nm (0.37 ft-lb)
Field Wire Maximum Resistance < 100 Ω
End-of-Line (EOL) Resistor Typically 4.7 kΩ ± 5% (0.25 W)
Max. Loop Capacitance (Hydrogen Areas A & B) 0.3 µF
Max. Loop Capacitance (Non-Hydrogen Areas C & D) 7 µF
Module Dimensions (L × W × H) 6.72 × 2.76 × 2.52 in
DIN Rail Compatibility TS32 / TS35 × 7.5
Required Rail Length 171 mm (6.73 in)
Installation Method DIN-rail mounting
Typical Applications Fire detection loops, gas detection input supervision, safety system field wiring

 