1
/
of
3
Allen-Bradley
Low stock: 10 left
Allen Bradley 1771-OWNA 32-Point Contact Output Module
Allen Bradley 1771-OWNA 32-Point Contact Output Module
Manufacturer: Allen-Bradley
Product No.: 1771-OWNA
Product Type: Relay Contact Output Module
Product Origin: USA
Payment: T/T
Weight: 1800g
Shipping port: Xiamen
Warranty: 12 months
Product Overview
The Allen-Bradley 1771-OWNA is a 32-point relay contact output module for the PLC-5 platform. It provides four groups of eight normally-open contacts rated at 24-138 V AC / 24-125 V DC, designed for switching resistive loads with complete isolation between field circuits and the backplane.
Technical Specs
- Output points: 32 (4 groups of 8), non-selectable N.O. contacts
- Voltage rating: 24-138 V AC RMS, 24-125 V DC
- Current rating: 1 A continuous per output, 4 A per group, 12 A per module
- Contact power rating: 30 W resistive at 45 °C, 15 W at 60 °C
- Backplane current: 2.5 A max, 1.8 A nominal
- Operate/release time: 5 ms (+1 ms) typical
- Switching frequency: 10 Hz max
- Wiring arm: 1771-WN
Key Features
- 32 normally-open relay contacts for flexible load switching
- Group isolation with individual commons per group
- Blown fuse indicator for quick fault diagnosis
- Suitable for resistive loads; not recommended for inductive or capacitive loads
FAQ
- Can the contacts be configured as N.C.? No, the OWNA provides non-selectable normally-open contacts only. For selectable N.O./N.C., use the 1771-OW.
- What is the maximum cable length? 1000 ft (304.8 m) for interconnect cables.
- Is it suitable for motor starters? It can drive motor starters within the 1 A per point and 30 W contact rating limits.
Installation Guide
- Power down the 1771 I/O chassis and field wiring.
- Insert the module into any slot except the leftmost.
- Attach the 1771-WN wiring arm and connect load wiring per the connection diagram.
- Verify keying bands are positioned between 6-8 and 16-18.
- Apply power and test each output group for proper switching.
Selection Tips
- Select 1771-OWNA for high-density relay contact applications requiring N.O. contacts.
- For 8-point selectable N.O./N.C. contacts, choose the 1771-OW.
- Limit loads to resistive types; inductive loads require external suppression.