Skip to product information
1 of 1

HONEYWELL

120 in stock

Honeywell FC-TSFIRE-1624 SAFE FIRE DET.INPUT FTA LM 24V 16CH CC

Honeywell FC-TSFIRE-1624 SAFE FIRE DET.INPUT FTA LM 24V 16CH CC

  • Manufacturer: HONEYWELL

  • Product No.: FC-TSFIRE-1624

  • Product Type: SAFE FIRE DET.INPUT FTA LM

  • Product Origin: USA

  • Payment: T/T

  • Weight: 1750g

  • Shipping port: Xiamen

  • Warranty: 12 months

Description

The Honeywell FC-TSFIRE-1624 is a 16-channel Safe Fire Detector Input Field Terminal Assembly (FTA) designed for use in Honeywell’s safety and fire detection systems. Operating at 24 VDC, it provides reliable signal conditioning and monitoring for fire detector loops across various industrial environments. The module supports supervised input wiring with end-of-line resistors, ensuring continuous integrity checks for open or shorted circuits. With robust electrical protection, clear termination specifications, and compatibility with hydrogen and non-hydrogen classified areas, it is ideal for safety-critical applications in oil & gas, petrochemical, and industrial process facilities.

Technical Data

Parameter Specification
Power Requirements 24 VDC (external)
Input Voltage Range 24 VDC +25% / –15%
Current Consumption (No Load) Typ. 11 mA at 24 VDC ext.
Number of Channels 16
Input Voltage (No Load) Typ. 23.5 VDC (at 24 VDC ext.)
Channel Resistance 680 Ω ± 5%
Shorted Current 35 mA (at 24 VDC ext.)
Relay Voltage Range 17–39 VDC
Relay Current Typ. 8.5 mA at 24 VDC
Termination Type Screw terminals
Max. Wire Diameter 2.5 mm² (AWG 14)
Wire Strip Length 7 mm (0.28 in)
Tightening Torque 0.5 Nm (0.37 ft-lb)
Field Wire Resistance < 100 Ω
End-of-Line (EOL) Resistor Example: 4.7 kΩ ± 5% (0.25 W)
Max. Loop Capacitance (Hydrogen Areas — Group A & B) 0.3 µF
Max. Loop Capacitance (Non-Hydrogen Areas — Group C & D) 7 µF
Module Dimensions (L × W × H) 6.72 × 2.76 × 2.52 in
DIN Rail Type TS32 / TS35 × 7.5
Required Rail Length 171 mm (6.73 in)

 

View full details